Kamstrup 602 Technical Description
Kamstrup 602 Installation Guide
Application
MULTICAL® 602 is an all-purpose energy calculator for heat and cooling together with almost any kind of pulsed flow sensors and with 2 or 4 wired temperature sensor pairs. Used together with Kamstrup ultrasonic flow sensor ULTRAFLOW®, even more advanced functions are available. On account of its pinpoint accuracy the meter registers precise consumption throughout the whole lifetime of the meter. The meter is maintenance-free and has a long lifetime which guarantees minimum yearly operating costs. MULTICAL® 602 is used for heat, cooling and combined heat /cooling measurement in all water-based systems with temperatures from 2°C to 180°C for heat and 2°C to 50°C for cooling.
Functionality
MULTICAL® 602 is used as heat meter together with the flow sensor, ULTRAFLOW® 54 and two temperature sensors. Flow sizes range from qp 0.6 m³/h to 1,000 m³/h. In cooling applications up to qp 100 m³/h the meter is connected to ULTRAFLOW® 14 and temperature sensors, whereas the meter is used together with ULTRAFLOW® 54 in cooling applications from qp 150 m³/h to qp 1,000 m³/h. The calculator can be used with flow parts up to qp 3,000 m³/h. MULTICAL® 602 is characterized by its complete range of communication modules and integral RTC (Real Time Clock), which make it easy to fit the meter into all applications independent of reading type. The meter can be fitted with LON, SIOX, M-Bus, a data module and the new solutions Metasys N2 and Ethernet/IP for wired communication. If the meter is to be integrated into a wireless network, you can select radio, Wireless M-Bus, Zigbee or one of Kamstrup‘s new modules: GSM/GPRS or High Power RadioRouter. The calculator‘s info codes and data loggers make up an invaluable tool for troubleshooting, error correction and analysis of energy consumption. The info codes constantly monitor a number of key functions in the meter, such as error in measuring system, power failure, leak, burst, or mounting of sensor in wrong flow direction. In such cases a flashing ”INFO” appears in the display. MULTICAL® 602 saves consumption data on a yearly, monthly, daily and hourly basis, which provides the operations manager with a complete performance analysis.
Operations optimisation
In case of power failure data is backed up, thus securing billing of consumption data. If the meter is supplied with battery, the battery lifetime has been considerably increased – up to 13 years incl. Wireless M-Bus. Finally, MULTICAL® 602 with ULTRAFLOW® and the precisely matched temperature sensors guarantee accurate measuring results even at minimal temperature differences. The flow sensor‘s long-term stability and accuracy are not influenced by flow velocity, flow disturbances or wear, which guarantees the required optimisation in operation and reduction of costs.
Unlimited communication
MULTICAL® 602 offers you a complete range of communication modules. The meter can be fitted with LON, SIOX, M-Bus, a data module and the new solutions Metasys N2 and Ethernet/IP for wired communication. If the meter is to be integrated in a wireless network, you can select radio, Wireless M-Bus, ZigBee, or new options like: GSM/GPRS or High-Power RadioRouter with High-Power supply. – MULTICAL® 602 provides unlimited communication.
Sharp analysis
MULTICAL® 602 is your guarantee that power supply, leakages and bursts are monitored and appear in the display in the form of an info code. An info logger registers and stores all irregularities and changes. Furthermore MULTICAL® 602 is fitted with an integral RTC and saves yearly, monthly, daily and hourly loggers, which you easily read and analyse as part of your daily operations optimisation.
Measurable saving
In case of power failure data is backed up, thus securing billing of consumption data. If the meter is fitted with a battery, the battery lifetime is prolonged to 13 years incl. Wireless M-Bus reading. MULTICAL® 602 is your guarantee that consumption data is accurately and constantly billed during the meter’s whole lifetime without need for service checks. The operating costs are minimal and cost saving thereby a reality.